Skip to main content

Table 3 Simulation results of the proposed scheme

From: Fault identification scheme for protection and adaptive reclosing in a hybrid multi-terminal HVDC system

Fault area/properties (P or T)

Zero passing characteristics

(b/a)

Fault isolation results

Fault distance (km)

Permanent fault?

f1-30/P

Y/Y

T1

29.98

Y

f1-30/T

Y/Y

T1

− 959.96

N

f1-250/P

Y/Y

T1

248.87

Y

f1-250/T

Y/Y

T1

− 961.34

N

f1-500/P

Y/Y

T1

499.71

Y

f1-500/T

Y/Y

T1

− 969.98

N

f2-30/P

N/N

T2

30.00

Y

f2-30/T

N/N

T2

− 945.85

N

f2-250/P

N/N

T2

249.54

Y

f2-250/T

N/N

T2

− 967.64

N

f2-500/P

N/N

T2

498.66

Y

f2-500/T

N/N

T2

− 973.41

N

f3/P

N/Y

T3

Y