Protection | Without LVRT | LVRT | |||
---|---|---|---|---|---|
Settings | Time(s) | Settings(UN) | Time(s) | ||
Voltage violation protection | Upper limit protection | 1.15UN | 0Â s | 1.15UN | 0 |
1.10UN | 0.1 | 1.10UN | 2 | ||
Lower limit protection | 0.9UN | 0.1 | 0.9UN | 2.2 | |
0.5UN | 1.3 | ||||
0.2UN | 0.66 | ||||
Frequency protection | Upper limit protection | 50.5Hz | 0.1 | 52.5Hz | 2 |
Lower limit protection | 49.5Hz | 0.1 | 47.5Hz | 2 | |
Over current protection | Primary section | Phase to phase fault | 0 | NO | |
Zone III | 2IN | 1.5 | NO | ||
Voltage unbalance protection | 0.1UN | 0.3 | 0.1UN | 3 | |
Current unbalance protection | 0.15IN | 0.1 | 0.15IN | 1 |