Table 2 Sequence of Relay Operation of feeder 2 with conventional overcurrent protection scheme

From: Adaptive overcurrent protection scheme coordination in presence of distributed generation using radial basis neural network

Faulted Bus 33 without DG

Faulted Bus 33 with DG penetration

Relay

Time dial

Pickup tap

Short circuit current (kA)

Time operation (ms)

Operation area

Short circuit current (kA)

Time operation (ms)

Operation area

OR 32

0.07

2.400

0.823

198

Feeder 2

1.159

18

Maloperation

OR 31

0.10

2.450

0.795

430

Feeder 2

1.132

29

Maloperation

OR 30

0.13

2.460

0.755

757

Feeder 2

1.095

44.4

Maloperation

OR 29

0.18

2.470

0.624

1405

Feeder 2

0.825

69.5

Maloperation

OR 28

0.19

2.480

0.596

2532

Feeder 2

0.804

117

Maloperation

OR 27

0.28

2.490

0.585

4421

Feeder 2

0.796

185

Maloperation

OR 26

0.5

2.500

0.575

6536

Feeder 2

0.790

351

Maloperation

OR 25

0.68

2.520

0.566

10,091

Feeder 2

0.784

579

Maloperation