Table 2 Summarized results

From: “Adaptive virtual synchronous generator control using optimized bang-bang for Islanded microgrid stability improvement”

 

Controller

Nadir (Hz)

ROCOF (Hz/s)

ITAE (Hz.s2)

Restoration time (s)

HESS energy (MJ)

Load increment

CP-VSG

49.868

0.2599

2.3933

4.2

0.37

BB-AH-VSG

49.917

0.1574

2.5339

6.5

0.85

OBB-AHD-VSG

49.921

0.1167

2.4538

4.4

0.69

Load decrement

CP-VSG

50.133

0.2592

2.3979

4.2

− 0.5

BB-AH-VSG

50.089

0.1581

2.5243

6.8

− 1

OBB-AHD-VSG

50.087

0.1162

2.4676

4.5

− 0.8

Solar decrement

CP-VSG

49.911

0.1731

1.5721

3.7

0.23

BB-AH-VSG

49.927

0.1033

1.6339

5.7

0.54

OBB-AHD-VSG

49.931

0.0773

1.5870

3.99

0.44

Solar increment

CP-VSG

50.090

0.1739

1.5744

3.7

− 0.3

BB-AH-VSG

50.072

0.1028

1.6648

5.8

− 0.7

OBB-AHD-VSG

50.070

0.0773

1.5913

4.0

− 0.6

PVG disconnecting

CP-VSG

49.568

0.8432

7.5091

5.60

1.29

BB-AH-VSG

49.734

0.5098

8.1568

9.2

2.81

OBB-AHD-VSG

49.800

0.3777

7.8742

5.55

2.24

PVG connecting

CP-VSG

50.396

0.7668

6.8500

5.54

− 1.3

BB-AH-VSG

50.243

0.4608

7.2996

9.0

− 2.7

OBB-AHD-VSG

50.186

0.3463

7.1539

5.36