Table 1 Comparative analysis of performance indices for the different scenarios

From: MPC-based LFC for interconnected power systems with PVA and ESS under model uncertainty and communication delay

Scenarios

Methods

Performance indices

ISE

IAE

ITSE

ITAE

No.1

Compared

0.8294

6.2448

5.8821

71.3548

(Case 1)

Proposed

0.0509

0.4761

0.0320

2.9937

No.1

Compared

22.4975

77.6274

1395.9515

5210.5255

(Case 2)

Proposed

0.0293

0.2560

2.2240

17.2418

No.2

Compared

2.0842

7.6199

9.0758

72.6244

 

Proposed

0.1544

0.8172

0.1452

2.0523

No.3

Compared

0.8392

6.2576

5.8845

71.2832

(Case 1)

Proposed

0.0550

0.4854

0.0344

2.9629

No.3

Compared

0.8220

6.2355

5.8857

71.4290

(Case 2)

Proposed

0.0470

0.4583

0.0297

2.9151

2*No.4

Compared

4.1575

14.6230

30.8214

184.3838

 

Proposed

0.0389

0.3197

0.0167

2.7693

  1. Bold values indicate the best value of each performance indice in the different control methods