Skip to main content

Table1 Advance Time and Result for SCF Prediction

From: An improved prediction method of subsequent commutation failure of an LCC-HVDC considering sequential control response

Fault severity (/%)

Method 1

Method 2

Method 3

Occurrence time of SCF (/s)

Prediction result (F/T)

Advance time (/ms)

Prediction result (F/T)

Advance time (/ms)

Prediction result (F/T)

Advance time (/ms)

15

T

–

T

–

T

–

–

25

T

–

F

–

T

–

–

35

F

–

F

–

T

–

–

45

T

69.3

T

80.3

T

60.3

1.1213

55

T

73.5

T

81.5

T

65.5

1.1215

65

T

79.7

T

84.7

T

67.7

1.1217

75

T

82.1

T

87.1

T

72.1

1.1211