Table 6 Mode-3 eigenvalue at varying series compensation level and wind speed with BESSDCL

From: Battery energy storage-based system damping controller for alleviating sub-synchronous oscillations in a DFIG-based wind power plant

Compensation

Wind speed (m/s)

Mode 3

Eigenvalue

Frequency(Hz)

40%

7

− 3.0 ± j255.9

40.74

9

− 3.04 ± j255.84

40.74

11

− 3.09 ± j255.8

40.73

50%

7

− 1.5 ± j229.23

36.50

9

− 1.54 ± j229.2

36.49

11

− 1.6 ± j229.1

36.48

60%

7

− 1.04 ± j207

32.96

9

− 1.09 ± j206.8

32.92

11

− 1.16 ± j206.82

32.93