Skip to main content

Table 4 Mode-3 eigenvalue at varying percentage of series compensation and wind speed

From: Battery energy storage-based system damping controller for alleviating sub-synchronous oscillations in a DFIG-based wind power plant

Compensation

Wind speed (m/s)

Mode 3

Eigenvalue

Frequency (Hz)

40%

7

0.01 ± j207

32.96

9

− 0.04 ± j206.9

32.94

11

− 0.12 ± j206.8

32.92

50%

7

1.66 ± j187.8

29.90

9

1.56 ± j187.7

29.87

11

1.43 ± j187.5

29.84

60%

7

3.26 ± j170.9

27.25

9

3.15 ± j170.7

27.14

11

2.95 ± j170.4

27.18