Skip to main content

Table 3 Eigenvalues of the study system model with 50% fsc level and 7 m/s wind speed

From: Battery energy storage-based system damping controller for alleviating sub-synchronous oscillations in a DFIG-based wind power plant

Modes

Eigenvalue

Frequency (Hz)

Description

Mode 1

− 1790 ± j889

141

Very high frequency

Mode 2

− 19.2 ± j568.2

90.4

Super-synchronous

Mode 3

1.6 ± j187.8

29.9

SSR

Mode 4

− 0.63 ± j18.8

2.86

Electromechanical

Mode 5

− 52.4 ± j7.9

1.25

Torsional mode

Mode 6

− 6.41 ± j8.6

1.36

Torsional mode