Table 2 General comparison between ACCB and DCCB

From: Circuit breakers in HVDC systems: state-of-the-art review and future trends

 

ACCB

DCCB

Interruption time

Tens of milliseconds

(80–100 ms)

2–10 ms

Interruption mechanism

Utilizing natural zero crossing in fault current to extinguish the arc and interrupt the AC fault current

Utilizing additional branches to create a current zero crossing for the fault current interruption

Max. breaking current

40–60 kA

16–25 kA

Standardization

IEEE c37.06

No standards for DCCB

Development state

Commercially available

In research and development stage