Table 1 Simulation parameters

From: Adaptive H event-triggered load frequency control in islanded microgirds with limited spinning reserve constraints

Parameters

Values

Equivalent rotational inertia (2H)

3 p.u.·s

Equivalent damping coefficient (D)

1 p.u.·Hz

Droop coefficient of DG (RDG)

3 Hz/p.u

Time constant of governor (Tg)

0.08 s

Time constant of turbine (Tt)

0.4 s

Time constant of ESS (TESS)

0.04 s

Maximum spinning reserve (ΔPrmax)

0.2 p.u

Participation factors (α, β)

(0.7, 0.3)

Rated capacities (SDG, SESS)

200, 45 kVA

Maximum delay (d)

50 ms

Maximum rated frequency deviation (|Δf|max_rated)

0.2 Hz

H damping coefficient (γ)

7.5

Weighting coefficients (σ1, σ2)

(0.3, 0.7)

Step size (θ)

0.001

Termination threshold of iteration (χ)

0.001

Scaling factor (εmin, εmax)

(0.7, 1.3)

Sampling period (Ts)

0.1 s