Table 4 Simulation results for different fault types

From: Single-ended protection method for hybrid HVDC transmission line based on transient voltage characteristic frequency band

Fault type

Transition resistance (Ω)

Fault distance (km)

ΔE(105)

F

Discriminatory result

Positive pole fault

0.01

800

18.9

1.79

Positive pole fault

Negative pole fault

0.01

800

18.1

0.56

Negative pole fault

Pole-to-pole fault

0.01

800

132

1.04

Pole-to-pole fault

External fault

0.01

0

1.55

–

External fault

AC fault

0.01

–

0.03

–

External fault