Table 2 The frequency band energies of different fault types

From: Single-ended protection method for hybrid HVDC transmission line based on transient voltage characteristic frequency band

 

Fault type

E5/105

E6/104

E7/103

E8/104

E9/104

E10/103

E11/103

E12/103

E13/103

â–³E/105

Internal

50 km/0.01 Ω

41.024

66.502

957.341

119.012

136.023

496.435

155.421

535.241

720.412

101.826

50 km/500 Ω

2.613

2.052

151.214

1.073

10.824

72.262

56.424

34.709

1.971

7.1737

800 km/0.01 Ω

6.832

7.972

378.346

12.243

15.641

155.364

269.542

26.324

21.424

18.927

800 km/500 Ω

2.391

4.594

12.943

72.251

1.791

12.324

11.714

3.871

2.416

10.687

External

0.01 Ω

0.267

1.983

31.421

5.424

0.715

2.731

9.099

0.013

3.828

1.551

500 Ω

0.084

0.007

0.227

0.223

0.011

0.033

0.021

0.010

0.048

0.112

A phase fault to ground/0.01 Ω

0.005

0.031

0.011

0.007

0.002

0.006

0.001

0.002

0.010

0.009

AB phase fault to ground/500 Ω

0.011

0.095

0.277

0.032

0.001

0.044

0.032

0.014

0.006

0.028

ABC phase fault/0.01 Ω

0.032

0.035

0.171

0.149

0.009

0.415

0.218

0.208

0.339

0.065