Table 3 Heavy reactive power at some load buses of the IEEE 30-bus test system

From: A novel collapse prediction index for voltage stability analysis and contingency ranking in power systems

Bus no.

Reactive power (MVAr)

Most critical lines

Lines (from–to)

NCPI

Lmn

FVSI

LQP

NLSI

VSLI

Bus-26

31.5

26–25

26–25

1.0086

0.8633

1.0055

0.6814

0.7459

0.7835

Bus-30

34.15

30–27

30–27

1.0091

0.9726

1.0038

0.7384

0.9528

0.9593

   

30–29

0.8119

0.7822

0.8025

0.6244

0.7394

0.7459

Bus-14

96.5

14–15

14–15

1.0018

0.7776

0.9943

0.4405

0.5328

0.5763

   

14–12

0.8540

0.7786

0.8540

0.6915

0.6891

0.7185

Bus-24

114

24–22

24–22

1.0020

0.8666

0.9986

0.6932

0.7597

0.7943

   

24–23

0.8101

0.7478

0.8097

0.6500

0.6697

0.6902

   

24–25

0.7517

0.6815

0.7517

0.5646

0.5715

0.5962

Bus-9

291.5

9–11

9–11

0.9807

0.9807

0.9807

0.9807

0.9807

0.9807

   

9–6

0.9786

0.9757

0.9719

0.9651

0.9719

0.9206

   

9–10

0.5930

0.5892

0.5881

0.5832

0.5881

0.5930

Bus-28

364

28–8

28–8

0.9981

0.9350

0.9917

0.8962

0.8957

0.9108

   

28–6

0.8575

0.8314

0.8569

0.7893

0.8072

0.8067

   

28–27

0.3405

0.3004

0.2964

0.2523

0.2964

0.4313

Bus-3

410

3–1

3–1

0.9994

0.9964

0.9435

0.7943

0.9913

0.9967

   

3–4

0.8595

0.7877

0.8508

0.7573

0.7008

0.7468