Table 12 Contingency ranking and analysis of the IEEE 118-bus system with two lines outages and pre-specified reactive power load at nodes 11, 20, 30, 33, 51, 75 and 96

From: A novel collapse prediction index for voltage stability analysis and contingency ranking in power systems

Pre-specified reactive power load: Q11 = 872 MVAr, Q20 = 115, Q30 = 700 MVAr, Q33 = 150MVAr, Q51 = 165 MVAr, Q75 = 550MVAr, and Q96 = 343 MVAr

Lines outages (N-2)

The rank of lines outages

Rank of each outage

Most stressed lines (from–to)

NCPI

Lmn

FVSI

LQP

NLSI

VSLI

96–97

75–74

1

1

75–70

0.9377

0.8722

0.9311

0.8523

0.8077

0.8437

 

2

75–69

0.9356

0.9230

0.8815

0.7099

0.9330

0.9271

 

3

75–77

0.9079

0.8871

0.8966

0.7985

0.8808

0.8722

 

4

96–80

0.7021

0.6973

0.6987

0.6673

0.6951

0.6842

 

5

30–26

0.7007

0.6297

0.5840

0.4560

0.6419

0.6382

30–8

96–82

2

1

30–26

0.8981

0.8586

0.7896

0.6618

0.8435

0.8516

 

2

96–80

0.7343

0.7286

0.7314

0.6991

0.7249

0.7146

 

3

75–69

0.6635

0.6355

0.5812

0.4369

0.6950

0.7072

75–69

13–11

3

1

30–26

0.7011

0.6330

0.5882

0.4642

0.6451

0.6378

 

2

75–77

0.6747

0.6334

0.5766

0.4340

0.6925

0.7085

 

3

96–80

0.5691

0.5663

0.5657

0.5405

0.5669

0.5544