Skip to main content

Table 2 Equivalent circuit parameters for [18, 35, 37] and this paper

From: A hybrid circuit breaker with fault current limiter circuit in a VSC-HVDC application

Case study

Parameter

Value

CS1,CS2,CS3,CS4

Terminal voltage (Vdc)/kV

200

CS1,CS2,CS3,CS4

Line current (Idc)/kA

0.5

CS1,CS2,CS3,CS4

Breaker impedance (Lb)/mH

38.4

CS1,CS2,CS3,CS4

Considered distance of fault/km

100

CS1,S2,CS3,CS4

Resistance per unit length/Ω/km

0.035

CS1,CS2,CS3,CS4

Inductance per unit length/mH/km

0.156

CS1,S2,CS3,CS4

Load resistance/Ω

400

CS3

CLIs value (L1 = L2 = L3)/mH

100

CS2

HCLC inductance/mH

100

HCLC resistance/Ω

50

CS4

CLIs value (L1 = L2 = L3)/mH

100