Skip to main content

Table 10 Optimal relay setting for common operating mode in 18 bus microgrid system using GA

From: Coordination of dual setting overcurrent relays in microgrid with optimally determined relay characteristics for dual operating modes

Relay RCI Forward Reverse Relay RCI Forward Reverse
TMS PS TMS PS TMS PS TMS PS
1 2 0.2909 1.1371 1.1000 1.9998 23 1 0.2277 0.5167 1.1000 1.9998
2 2 0.1 1.7002 0.4104 0.5510 24 2 0.4351 0.9222 1.1000 1.0659
3 2 0.1477 1.7122 1.1000 2.0000 25 2 0.1581 1.5164 1.1000 0.6721
4 2 1.0844 0.5740 0.7170 0.5913 26 2 0.5009 0.6876 1.1000 2.0000
5 2 0.8237 0.7349 1.1000 2.0000 27 2 0.4578 0.9954 1.0751 1.9645
6 1 0.2503 0.5144 1.0034 0.7500 28 2 0.1000 1.9102 1.1000 2.0000
7 2 0.6753 0.7578 1.1000 2.0000 29 2 0.5285 0.7757 1.1000 1.9953
8 2 0.2382 1.1168 1.1000 1.6350 30 2 0.4732 0.8708 1.0933 1.9979
9 2 0.5338 0.8283 1.1000 2.0000 31 2 0.4841 0.9310 0.9246 1.4508
10 2 1.0805 0.5953 1.1000 0.5156 32 2 0.1660 1.5015 1.1000 2.0000
11 1 0.2643 0.5162 1.1000 1.1119 33 2 0.7823 0.7869 1.1000 2.0000
12 2 0.2656 1.3253 1.1000 2.0000 34 2 1.0812 0.5786 1.1000 1.9987
13 2 1.0956 0.6344 1.1000 1.8827 35 2 0.3466 1.0587 1.1000 1.2698
14 2 0.8333 0.6044 1.1000 2.0000 36 2 0.2712 0.5864 1.1000 0.7618
15 2 0.3386 1.1727 0.1061 0.5050 37 2 0.2140 1.5094 0.1841 1.3251
16 2 1.0961 0.5312 1.1000 2.0000 38 1 0.2141 0.5218 1.1000 1.9983
17 2 0.1610 1.5053 1.1000 2.0000 39 2 0.3391 1.1641 1.1000 2.0000
18 2 1.0198 0.6835 1.1000 1.9844 40 2 1.0323 0.6713 1.1000 2.0000
19 2 0.3944 0.9916 1.1000 1.9985 41 2 1.0477 0.6434 1.1000 1.9999
20 2 0.9609 0.5456 1.0377 1.3120 42 3 0.1001 0.5000 1.1000 2.0000
21 2 0.5839 0.7671 1.0999 2.0000 43 2 1.0830 0.5672 1.1000 0.8326
22 2 0.2362 1.2411 1.1000 2.0000 44 2 0.9623 0.6789 1.1000 2.0000
Top 4.4472 (s)