Table 6 Quantitative assessment of transient performance under step change of active power

From: High performance decoupled active and reactive power control for three-phase grid-tied inverters using model predictive control

Mode of operation

Parameter

Value

Fixed

weight factors

Variable

weight factors

Step change in active power

(Pref: 0 → 10 kW)

(Qref is zero VAR)

Settling time [ms]

1.77

1.82

Max.│Cross coupling on Q│ [kVAR]

≅ 1.60

≅ 0.18

Peak overshoot of P

nil

nil

Weight factor wp

1

0.1

Weight factor wq

1

1

Steady state PF*

≅ 0.999

≅ 0.999

Worst PF during cross coupling

≅ 0.982

≅ 0.990

THD of current* [%]

≅ 3.350

≅ 3.350