Table 5 Quantitative assessment of steady state performance at Zero PF (Pref = 0 W, Qref = 10 kVAR)

From: High performance decoupled active and reactive power control for three-phase grid-tied inverters using model predictive control

Parameter

Value

Average value of reactive power

QAVG [VAR]

10,005

Worst value of reactive power ripple

∆Q = (Qref - Qactual) [VAR]

480

Percentage of reactive power ripple

100x∆Q/Qref) [%]

4.80

Percentage of reactive power deviation

100 x (Qref - QAVG)/Qref [%]

- 0.05

Average value of active power

PAVG [W]

−100.6

Worst value of active power ripple

∆P = (Pref - Pactual) [W]

369

Actual PF

Cos (tan−1[Q/P)]

0.01

Total harmonic distortion

THD of grid current [%]

3.12