Skip to main content

Table 1 MMCC power system parameters

From: Inter-cluster voltage balancing control of a delta connected modular multilevel cascaded converter under unbalanced grid voltage

Symbol

Quantity

Value

Vs

Grid rms voltage

3.535 kV

S

Grid rated power

1.2MVA

Csm

Sub-module Capacitance

1.12mF

Lac, Rac

Filter

8 mH, 2 Ω

Vdc

Sub-module DC voltage

2500 V

N

Number of sub-modules per phase

4

fc

Carrier frequency

1000 Hz

fs

Sampling frequency

10,000 Hz