Table 3 Influence of system asymmetry on neutral voltage and sequence current ratio

From: Fault protection method of single-phase break for distribution network considering the influence of neutral grounding modes

Group

Ungrounded

Arc suppression coil grounded

Low resistance grounded

λ(%)

Uunb(V)

UO(V)

n1

λ(%)

Uunb(V)

UO(V)

n1

λ(%)

Uunb(V)

UO(V)

n1

1

0

0.28

410.55

1

0

2.26

4016.37

1

0

0

48.31

1

2

0.29

16.05

412.44

1

2.88

113.27

4058.79

1

0.03

1.97

50.10

1

3

0.43

23.86

418.64

1

4.30

235.21

4101.22

1

0.05

2.91

51.15

1

4

0.83

45.61

437.84

1

8.25

403.05

4115.36

1

0.09

5.59

53.46

1

5

1.10

60.88

454.32

1

10.9

551.54

4131.93

1

0.12

7.42

55.15

1