Table 9 Performance of distance relay RA with PAZSD methodology for different faults with FR = 4.9 Ω at different distances

From: PMU based adaptive zone settings of distance relays for protection of multi-terminal transmission lines

Fault Condition

Impedance seen by the relay RA

Current Coefficients

New Zone Setting of

Performance of RA with proposed methodology

K 1

K 2

K 3

Zone 1

Zone 2

Zone of fault detection is?

Is detected zone correct? (Y/N)

LLG Fault at 50 km

3.937  63.990

1.7266

1.3281

1.2969

40.22160.36°

75.41460.36°

Zone 1

Y

LLL Fault at 50 km

8.436  22.50

1.3281

1.3516

1.3906

32.39460.36°

60.73860.36°

Zone 1

Y

LG Fault at 150 km

20.52  45.070

2.5078

1.9219

2.1875

58.41860.36°

109.53560.36°

Zone 1

Y

LL Fault at 150 km

16.296  43.510

2.7656

2.5313

2.0703

64.42460.36°

120.79560.36°

Zone 1

Y

LL Fault at 250 km

38.814  68.430

1.7734

4.1172

4.7578

110.83260.36°

207.80960.36°

Zone 1

Y

LLL Fault at 250 km

39.5  67.690

3.3516

3.9453

4.3516

101.36960.36°

190.06760.36°

Zone 1

Y

LLG Fault at 300 km

52.864   − 273.090

2.2109

4.5156

5.1484

119.93060.36°

224.87060.36°

Zone 1

Y

LLL Fault at 300 km

52.268  65.3030

3.5313

3.9063

4.6016

107.19360.36°

200.98760.36°

Zone 1

Y

LG Fault at 350 km

79.285  68.280

2.7891

4.5469

2.8516

105.91960.36°

198.59860.36°

Zone 2

Y

LLG Fault at 350 km

80.614  68.660

4.3359

4.75

5.0547

117.74860.36°

220.77760.36°

Zone 2

Y