Table 7 Performance of the distance relay RA with PAZSD methodology for different faults with FR = 0.2 Ω at different distances

From: PMU based adaptive zone settings of distance relays for protection of multi-terminal transmission lines

Fault Condition

Impedance seen by the relay RA

Current Coefficients

New Zone Setting of

Performance of RA with proposed methodology

K 1

K 2

K 3

Zone 1

Zone 2

Zone of fault detection is?

Is detected zone correct? (Y/N)

LG Fault at 50 km

4.01163.5990

1.2656

1.6712

1.5703

38.93060.36°

72.99460.36°

Zone 1

Y

LL Fault at 50 km

3.933  60.950

1.5703

1.3281

1.2734

36.58060.36°

68.58760.36°

Zone 1

Y

LLG Fault at 150 km

11.765  58.050

2.8125

2.75

2.2422

65.51660.36°

65.51660.36°

Zone 1

Y

LLL Fault at 150 km

11.566  61.690

1.7854

1.2134

1.6457

41.5960.36°

77.982760.36°

Zone 1

Y

LG Fault at 250 km

31.934  84.010

1.9766

4.8047

1.875

111.92460.36°

209.85860.36°

Zone 1

Y

LL Fault at 250 km

32.092  84.440

4.3359

5.1328

2.0313

119.56760.36°

224.18860.36°

Zone 1

Y

LLG Fault at 250 km

35.082   − 273.070

1.6484

2.2266

5.4453

126.84760.36°

237.83860.36°

Zone 1

Y

LLL Fault at 250 km

34.394  84.890

4.9063

5.1719

5.7969

135.03760.36°

253.19560.36°

Zone 1

Y

LLG Fault at 300 km

48.136  80.370

2.4688

4.0469

4.375

101.91460.36°

191.09060.36°

Zone 1

Y

LG Fault at 350 km

75.180  83.110

2.8906

5.2188

2.7188

121.57060.36°

227.94560.36°

Zone 2

Y

LL Fault at 350 km

82.706  83.210

2.6641

5.125

6.0469

140.86160.36°

264.11460.36°

Zone 2

Y

LLL Fault at 350 km

76.616  79.090

4.9609

5.5234

5.8047

128.66660.36°

241.24960.36°

Zone 2

Y