Table 5 Comparison of the relay trip timings (in ms) for full cycle window and half cycle window calculations for the microgrid subjected to various types of operating modes (GCM and IM), fault types, fault resistances, and faulted distribution lines, respectively

From: A fast time-frequency response based differential spectral energy protection of AC microgrids including fault location

Sl. no.

Microgrid operation mode

Fault Type

Fault Resistance (in Ω)

Fault Distance Ratio

(0–1) [×100] in %

Faulted

Line

Relay trip timing (in ms)

Full Window Calculation

Relay trip timing (in ms)

Half Window Calculation

Phase a

Phase b

Phase c

Phase a

Phase b

Phase c

1

GCM

(DG 1234

ON)

a-g

0.1

0.8

DL AB

10.6771

-

-

6.5104

-

-

2

b-g

1

0.7

-

9.8958

-

-

5.7292

-

3

c-g

10

0.6

-

-

9.8958

-

-

5.7292

4

ab-g

0.1

0.5

DL AE

10.9375

10.4167

-

6.7708

6.2500

-

5

bc-g

1

0.4

-

10.1563

9.8958

-

5.9896

5.7292

6

ca-g

10

0.3

12.2396

-

9.8958

8.0729

-

5.7292

7

abc-g

0.1

0.2

DL BE

10.9375

10.1563

9.3750

6.7708

5.9896

5.2083

8

abc-g

1

0.1

10.6771

9.8958

9.3750

6.5104

5.7292

5.2083

9

abc-g

10

0.5

10.9375

10.4167

9.8958

6.7708

6.2500

5.7292

10

GCM

(DG 1234

OFF)

a-g

0.1

0.1

DL AB

9.8958

-

-

5.7292

-

-

11

b-g

1

0.2

-

9.8958

-

-

5.7292

-

12

c-g

10

0.3

-

-

9.6354

-

-

5.4687

13

ab-g

0.1

0.4

DL AE

10.6771

10.1563

-

6.5104

5.9896

-

14

bc-g

1

0.5

-

9.8958

9.6354

-

5.7292

5.4687

15

ca-g

10

0.6

9.6354

-

9.6354

5.4687

-

5.4687

16

abc-g

0.1

0.7

DL BE

9.8958

10.6771

9.6354

5.7292

6.5104

5.4687

17

abc-g

1

0.8

9.8958

10.4167

9.6354

5.7292

6.2500

5.4687

18

abc-g

10

0.5

9.6354

10.9375

9.6354

5.4687

6.7708

5.4687

19

IM

(DG 1234

ON)

a-g

0.1

0.1

DL BC

13.0208

-

-

8.8542

-

-

20

b-g

1

0.2

-

10.1563

-

-

5.9896

-

21

c-g

10

0.3

-

-

11.4583

-

-

7.2917

22

ab-g

0.1

0.4

DL CD

9.8958

9.1146

-

5.7292

4.9479

-

23

bc-g

1

0.5

-

9.1146

9.1146

-

4.9479

4.9479

24

ca-g

10

0.6

11.4583

-

9.6354

7.2917

-

5.4687

25

abc-g

0.1

0.7

DL BE

12.7604

9.8958

9.6354

8.5937

5.7292

5.4687

26

abc-g

1

0.8

12.7604

9.8958

9.6354

8.5937

5.7292

5.4687

27

abc-g

10

0.5

12.5000

9.8958

9.6354

8.3333

5.7292

5.4687

28

IM

(DG 1

ON)

a-g

0.1

0.8

DL BC

11.1979

-

-

7.0313

-

-

29

b-g

1

0.7

-

14.8438

-

-

10.6771

-

30

c-g

10

0.6

-

-

11.1979

-

-

7.0313

31

ab-g

0.1

0.5

DL CD

11.1979

10.4167

-

7.0313

6.2500

-

32

bc-g

1

0.4

-

10.4167

9.8958

-

6.2500

5.7292

33

ca-g

10

0.3

10.4167

-

10.4167

6.25

-

6.25

34

abc-g

0.1

0.2

DL BE

10.1563

9.6354

10.1563

5.9896

5.4687

5.9896

35

abc-g

1

0.1

9.8958

9.6354

10.1563

5.7292

5.7292

5.7292

36

abc-g

10

0.5

13.5417

9.8958

10.1563

9.375

5.7292

5.9896