Table 6 Simulation results for internal DC line faults

From: Novel transient-energy-based directional pilot protection method for HVDC line

Location

RF (Ω)

Pole

Rectifier station

Inverter station

Result

S m

Dir

S n

Dir

F1 (1 km)

10

+

−34.02

1

−10.51

1

Internal

-

−0.27

0

−2.44

1

Normal

200

+

−5.64

1

−1.91

1

Internal

-

/

/

−0.43

0

Normal

300

+

−3.24

1

−1.13

1

Internal

-

/

/

/

/

Normal

F2 (500 km)

10

+

−0.17

0

−0.64

0

Normal

-

−13.23

1

−9.33

1

Internal

200

+

/

/

−0.04

0

Normal

-

−2.85

1

−2.37

1

Internal

300

+

/

/

/

/

Normal

-

−1.70

1

−1.71

1

Internal

F3 (1000 km)

10

+

−24.96

1

−25.01

1

Internal

-

−25.21

1

−25.09

1

Internal

200

+

−8.13

1

−8.44

1

Internal

-

−8.20

1

−8.46

1

Internal

300

+

−5.37

1

−5.69

1

Internal

-

−5.40

1

−5.80

1

Internal