Table 4 Results for different reverse side fault during single-pole-tripping

From: A positive-sequence current based directional relaying approach for CCVT subsidence transient condition

Fault type

Fault location

in km

θ (rad), Fault resistance = 50 Ω

SIR = 0.2

SIR = 1

SIR = 5

SIR = 10

SIR = 30

c-g

5

−0.4201

−0.5444

−0.6910

−1.034

−1.276

c-g

100

−0.4213

−0.4160

−0.6337

−0.8548

−1.294

c-g

200

−0.4290

−0.4290

−0.6120

−1.0557

−1.380

c-g

245

−0.4107

−0.4107

−0.6094

−0.8571

−1.318

bc

5

−0.6531

−0.8536

−0.9889

−1.0347

−1.096

bc

100

−0.7162

−0.7149

−0.9585

−1.012

−1.156

bc

200

−0.7051

−0.7051

−0.9247

−0.9723

−0.944

bc

245

−0.6844

−0.6844

−0.8693

−0.8940

−0.969

bc-g

5

−0.5217

−0.7392

−0.9371

−1.0310

−1.223

bc-g

100

−0.5728

−0.5715

−0.8904

−0.9608

−1.157

bc-g

200

−0.5839

−0.5839

−0.8081

−0.8364

−0.808

bc-g

245

−0.5730

−0.5730

−0.7894

−0.8315

−0.892