Table 8 The line stability indices for the IEEE 118-bus system under heavy apparent power load

From: A novel collapse prediction index for voltage stability analysis and contingency ranking in power systems

Bus no.

Apparent power

P (MW), Q (MVAr)

Most critical lines

Lines (from–to)

NCPI

Lmn

FVSI

LQP

NLSI

VSLI

Bus-117

P = 137

Q = 106.2

117–12

117–12

0.9817

0.9405

0.7088

0.3653

0.8758

0.9792

Bus-20

P = 180

Q = 165

20–19

20–19

0.9789

0.8961

0.7869

0.5942

0.8934

0.9005

 

20–21

0.3478

0.2937

0.2721

0.1847

0.3734

0.3857

Bus-30

P = 920

Q = 710

30–26

30–26

0.9834

0.7737

0.5941

0.2027

0.6971

0.8922

 

30–8

0.8230

0.8191

0.8067

0.7812

0.8225

0.8042

 

30–38

0.8988

0.8868

0.6292

0.8722

0.4665

0.3874

 

30–17

0.5861

0.5844

0.5839

0.5818

0.5839

0.6663

Bus-50

P = 300

Q = 278

50–49

50–49

0.9920

0.9556

0.7231

0.3302

0.9220

0.9906

 

57–50

0.8579

0.8419

0.7866

0.6057

0.8670

0.8691

Bus-96

P = 570

Q = 490

96–80

96–80

0.9562

0.8734

0.6384

0.2567

0.8097

0.9958

 

96–94

0.7479

0.7312

0.6866

0.5546

0.7664

0.7809

 

96–97

0.6940

0.6077

0.5230

0.3136

0.6595

0.7790

 

96–82

0.6460

0.5950

0.5230

0.3474

0.6744

0.7325