Skip to main content

Table 6 The line stability indices for the IEEE 118-bus system under heavy active power load

From: A novel collapse prediction index for voltage stability analysis and contingency ranking in power systems

Bus No

Active power (MW)

Most Critical lines

Lines (from-to)

NCPI

Lmn

FVSI

LQP

NLSI

VSLI

Bus-13

500

13–15

13–15

1.0043

0.6722

0.2437

1.2909

0.2751

0.9904

   

13–11

0.7460

0.2414

0.1401

0.4783

0.5245

0.8220

Bus-17

1014

17–30

17–30

0.9332

0.4395

0.3954

0.9032

0.3954

0.0979

   

17–113

0.2336

0.2316

0.2295

0.2064

0.2459

0.2462

   

17–16

0.1278

0.1134

0.1096

0.0863

0.1671

0.1651

   

17–31

0.1162

0.0148

0.0131

0.0835

0.1904

0.2658

   

17–15

0.0409

0.0269

0.0258

0.0368

0.0442

0.0540

   

17–18

0.0408

0.0386

0.0381

0.0335

0.0601

0.0608

Bus-20

396.8

20–19

20–19

0.9721

0.5477

0.2854

0.7570

0.6897

0.9860

   

20–21

0.5292

0.3222

0.2648

0.5240

0.0412

0.2246

Bus-51

466

51–49

51–49

0.9637

0.7095

0.2064

1.2640

0.3610

0.9981

   

51–58

0.3480

0.1705

0.1361

0.0819

0.4109

0.5594

   

51–52

0.1473

0.1234

0.1165

0.0779

0.2123

0.2301

Bus-67

695

67–66

67–66

0.9389

0.2999

0.1076

1.1730

0.2696

0.9281

   

67–62

0.8464

0.3211

0.1762

0.5484

0.4856

0.8950