Skip to main content

Table 10 Contingency ranking and analysis of the IEEE 30-bus system with pre-specified reactive power load

From: A novel collapse prediction index for voltage stability analysis and contingency ranking in power systems

Prespecified reactive power load: Q12 = 148.9 MVAr, Q20 = 50.5MVAr, Q30 = 17.1 MVAr

Line outage

Rank of lines outages

Rank of each outage

Most stressed lines (from–to)

NCPI

Lmn

FVSI

LQP

NLSI

VSLI

29–27

1

1

30–27

0.9461

0.9005

0.8518

0.5430

0.8988

0.9001

 

2

12–4

0.6731

0.6231

0.6129

0.5527

0.6129

0.4069

 

3

28–27

0.5775

0.5433

0.5364

0.4953

0.5364

0.4602

12–4

2

1

12–13

0.8242

0.8242

0.8242

0.8242

0.8242

0.8242

 

2

6–10

0.6013

0.4775

0.4565

0.3118

0.4565

0.4825

30–29

3

1

30–27

0.8146

0.7742

0.7592

0.5326

0.7871

0.7878

 

2

12–4

0.6694

0.6213

0.6115

0.5536

0.6115

0.4032

 

3

28–27

0.5122

0.4805

0.4753

0.4384

0.4753

0.3922

20–19

4

1

20–10

0.6797

0.6421

0.6795

0.5645

0.5771

0.5901

 

2

12–4

0.6632

0.6067

0.5956

0.5282

0.5956

0.3948