Skip to main content

Table 1 The line stability indices for the IEEE 30-bus system in the base case loading

From: A novel collapse prediction index for voltage stability analysis and contingency ranking in power systems

Line

NCPI

Lmn

FVSI

LQP

NLSI

VSLI

6–4

0.0364

0.0333

0.0326

0.0334

0.0021

0.0049

6–28

0.0249

0.0242

0.0243

0.0221

0.0101

0.0049

9–11

0.1113

0.1113

0.1113

0.1113

0.1113

0.1113

16–17

0.0121

0.0119

0.0118

0.0098

0.0210

0.0211

18–15

0.0177

0.0169

0.0167

0.0129

0.0373

0.0377

20–10

0.0328

0.0315

0.0310

0.0247

0.0566

0.0574

21–10

0.0328

0.0323

0.0321

0.0259

0.0463

0.0465

25–24

0.0267

0.0263

0.0266

0.0199

0.0104

0.0106

24–23

0.0164

0.0162

0.0162

0.0130

0.0219

0.0219

30–27

0.0502

0.0415

0.0398

0.0245

0.1154

0.1205

30–29

0.0142

0.0126

0.0124

0.0086

0.0445

0.0454