Skip to main content

Table 2 The part model parameters and control system parameters

From: Frequency control of a wind-diesel system based on hybrid energy storage

The parameters of adjustable generator model

Parameter

Value

Parameter

Value

frate (Hz)

50

Kpi (Hz/MW)

1

Tpi (sec)

10

ri (Hz/MW)

0.05

Tchi (sec)

0.3

ni (MW/Hz)

0.425

Tgi (sec)

0.2

Tij (MW/Hz)

0.545

KEi (1/s)

1

PG-capacity (kW)

280

The parameters of HESS model

Parameter

Value

Parameter

Value

Rbs (Ω)

0.013

Rbt (Ω)

0.0167

α1°

15

α2°

25

XCO (Ω)

0.02744

Ed0 (kV)

2

KCA (kA/unitMW)

70

Kvd (kA/kV)

0.1

TC (s)

0.05

RU (Ω)

100

CU (F)

1

PBES-capacity (kW)

100

PUC-capacity (kW)

80

  

the parameters of WTG model

Parameter

Value

Parameter

Value

Ar (m)

14

J (kg*m2)

62,993

ρ (kg*m3)

1.225

V (V)

230.94

R1 (Ω)

0.00397

R2 (Ω)

0.00443

X1 (Ω)

0.00376

X2 (Ω)

0.0534

PGW (kW)

120

  

Response thresholds of the proposed control strategy

Parameter (p.u.)

Value (%)

Parameter (p.u.)

Value (%)

ACEN

0.12

ACEA

0.3

ACEE

0.5