Table 1 Sampled values protocol profiles according to IEC 61869-9:2016 Table 902.

From: Towards a standardisation for digital inputs and outputs of protection functions in IEC 60255 series

Digital output sample rates Hz Number of ASDUs per frame Digital output publishing rate frames/s Remarks
4000 1 4000 For use on 50 Hz systems backward compatible with 9-2LE guideline
4800 1 4800 For use on 60 Hz systems backward compatible with 9-2LE guideline, or 50 Hz systems backward compatible with 96 samples per nominal system frequent cycle
4800 2 2400 Preferred rate for general measuring and protective applictaions, regardless of the power system frequency
5760 1 5760 For applications on 60 Hz systems backward compatible with 96 samples per nominal system frequency cycle
12,800 8 1600 Deprecated, only for use on 50 Hz systems
14,400 6 2400 Preferred rate for quality metering applications, regardless of the power system frequency including instrument transformers for tiem critical low bandwidth d.c. control applications
15,360 8 1920 Deprecated, only for use on 60 Hz systems
96,000 1 96,000 Preferred rate for instrument transformers for high bandwidth d.c. control applications