From: A d-axis based current differential protection scheme for an active distribution network
Fault location | Fault type | Sdiff /kA | Sres /kA | Result |
---|---|---|---|---|
f3' | ABC | 256.79 | 50.71 | Internal fault |
AB | 158.13 | 31.21 | Internal fault | |
AB-g | 148.81 | 29.42 | Internal fault | |
f3'' | ABC | 194.70 | 38.29 | Internal fault |
AB | 116.47 | 22.87 | Internal fault | |
AB-g | 111.75 | 21.97 | Internal fault |