Skip to main content

Table 2 Simulation results of N3N4 when asymmetric faults occur at f3

From: A d-axis based current differential protection scheme for an active distribution network

Fault type

Rf /(Ω)

Sdiff /kA

Sres /kA

Result

Two-phase

0

134.07

26.41

Internal fault

Two-phase-ground

0

127.57

25.17

Internal fault

 

5

18.77

3.78

Internal fault

 

50

2.22

0.52

Internal fault