Skip to main content

Table 3 Different DC faults current threshold range under fault resistance and distance variations

From: A new protection scheme for PV-wind based DC-ring microgrid by using modified multifractal detrended fluctuation analysis

Different faults under Rf variation

Different faults under Fd variation

Type of fault

Fault range (A)

Fault range (A)

Min

Max

Min

Max

P-P

789

2151

518

1012

P-P-G

280

568

374

415

N-P-G

− 280

− 568

− 374

− 415

Series arc

11.4

20.8

13.8

16.7

Shunt arc

− 1.89

− 4.05

− 2.72

− 3.25