Skip to main content

Table 8 Common optimal relay setting using dual setting DOCR for 7-bus microgrid system

From: Coordination of dual setting overcurrent relays in microgrid with optimally determined relay characteristics for dual operating modes

Relay

Forward

Reverse

RCI

Relay

Forward

Reverse

RCI

TMS

PS

TMS

PS

TMS

PS

TMS

PS

R1

0.5071

0.595

0.1000

0.816

2

R9

0.2205

0.516

0.610

0.500

1

R2

0.6757

0.734

0.9420

1.649

2

R10

0.6688

0.500

1.1000

1.744

2

R3

0.1329

0.500

0.1188

0.500

1

R11

0.2159

1.502

1.1000

1.638

2

R4

0.1000

0.500

0.3501

1.657

3

R12

0.2540

0.500

1.0990

0.531

2

R5

0.7841

0.682

0.1626

0.504

2

R13

0.1614

1.594

1.1000

2.000

2

R6

0.1000

1.146

0.9213

1.500

1

R14

0.6022

0.500

0.1000

0.572

2

R7

0.2440

0.500

0.1610

0.622

2

R15

0.1000

1.211

0.2417

0.500

1

R8

0.2390

0.5000

1.1000

1.2920

1

R16

0.1333

0.5075

0.1475

0.8044

1

Top

1.68 (s)