Table 8 Common optimal relay setting using dual setting DOCR for 7-bus microgrid system

From: Coordination of dual setting overcurrent relays in microgrid with optimally determined relay characteristics for dual operating modes

Relay Forward Reverse RCI Relay Forward Reverse RCI
TMS PS TMS PS TMS PS TMS PS
R1 0.5071 0.595 0.1000 0.816 2 R9 0.2205 0.516 0.610 0.500 1
R2 0.6757 0.734 0.9420 1.649 2 R10 0.6688 0.500 1.1000 1.744 2
R3 0.1329 0.500 0.1188 0.500 1 R11 0.2159 1.502 1.1000 1.638 2
R4 0.1000 0.500 0.3501 1.657 3 R12 0.2540 0.500 1.0990 0.531 2
R5 0.7841 0.682 0.1626 0.504 2 R13 0.1614 1.594 1.1000 2.000 2
R6 0.1000 1.146 0.9213 1.500 1 R14 0.6022 0.500 0.1000 0.572 2
R7 0.2440 0.500 0.1610 0.622 2 R15 0.1000 1.211 0.2417 0.500 1
R8 0.2390 0.5000 1.1000 1.2920 1 R16 0.1333 0.5075 0.1475 0.8044 1
Top 1.68 (s)