Skip to main content

Table 1 Electromechanical modes

From: Effective damping of local low frequency oscillations in power systems integrated with bulk PV generation

Case

Electromechanical modes

Status

CFV

\(- 0.0003 \pm j8.6441\)

Stable

 

\(\omega_{d} = 1.3758 Hz\)

 
 

\(\zeta = 3.4706 \times 10^{ - 5}\)

 

AVR with deactivated PSS

\(+ 0.189 \pm j8.632\)

Unstable

 

\(\omega_{d} = 1.373Hz\)

 
 

\(\zeta = -\) 0.0219