Table 5 Fault current calculations/simulations under a two-phase fault at point f

From: Equivalent model of multi-type distributed generators under faults with fast-iterative calculation method based on improved PSO algorithm

 

Current from network-side

Current of IIDG

Positive sequence

Negative sequence

Positive sequence

Negative sequence

Amp/kA

Phase/°

Amp/kA

Phase/°

Amp/kA

Phase/°

Amp/kA

Phase/°

Theoretical calculations

1.9629

266.42

0.6715

107.65

0.658

74.30

0

/

Simulation results

1.9658

265.25

0.6732

108.48

0.66

74.83

0.038

− 76.16

 

Current of DFIG

Current at fault point

Positive sequence

Negative sequence

Positive sequence

Negative sequence

Amp/kA

Phase/°

Amp/kA

Phase/°

Amp/kA

Phase/°

Amp/kA

Phase/°

Theoretical calculations

0.647

47.33

0

/

0.805

110.15

0.805

110.15

Simulation results

0.6424

47.01

0.042

72.73

0.806

112.68

0.806

112.95