| Current from network-side | Current of IIDG | ||||||
---|---|---|---|---|---|---|---|---|
Positive sequence | Negative sequence | Positive sequence | Negative sequence | |||||
Amp/kA | Phase/° | Amp/kA | Phase/° | Amp/kA | Phase/° | Amp/kA | Phase/° | |
Theoretical calculations | 1.9629 | 266.42 | 0.6715 | 107.65 | 0.658 | 74.30 | 0 | / |
Simulation results | 1.9658 | 265.25 | 0.6732 | 108.48 | 0.66 | 74.83 | 0.038 | − 76.16 |
 | Current of DFIG | Current at fault point | ||||||
---|---|---|---|---|---|---|---|---|
Positive sequence | Negative sequence | Positive sequence | Negative sequence | |||||
Amp/kA | Phase/° | Amp/kA | Phase/° | Amp/kA | Phase/° | Amp/kA | Phase/° | |
Theoretical calculations | 0.647 | 47.33 | 0 | / | 0.805 | 110.15 | 0.805 | 110.15 |
Simulation results | 0.6424 | 47.01 | 0.042 | 72.73 | 0.806 | 112.68 | 0.806 | 112.95 |