Table 7 Results of the proposed positioning method (φ = 30, arc suppression coil grounding system)

From: A novel fault section locating method based on distance matching degree in distribution network

Rg F HSAB HSBC HSCD HSDE HSEF section
0 F1 0.4682 / / / / AB
F2 0.9498 0.4346 / / / BC
F3 0.9281 0.9564 0.4404 / / CD
F4 0.9411 0.9365 0.9068 0.4573 / DE
F5 0.9321 0.9121 0.9274 0.9582 0.4562 EF
100 F1 0.4061 / / / / AB
F2 0.9192 0.4466 / / / BC
F3 0.9099 0.9109 0.4599 / / CD
F4 0.9147 0.9577 0.9688 0.4511 / DE
F5 0.9192 0.9296 0.9066 0.9419 0.4330 EF
500 F1 0.4334 / / / / AB
F2 0.9040 0.4446 / / / BC
F3 0.9722 0.9422 0.4271 / / CD
F4 0.9756 0.9239 0.9425 0.4134 / DE
F5 0.9393 0.9453 0.9475 0.9445 0.4662 EF