Table 9 Results of the proposed positioning method (φ = 60, arc suppression coil grounding system)

From: A novel fault section locating method based on distance matching degree in distribution network

Rg F HSAB HSBC HSCD HSDE HSEF section
0 F1 0.4624 / / / / AB
F2 0.9312 0.4624 / / / BC
F3 0.9193 0.9621 0.4020 / / CD
F4 0.9323 0.9506 0.9105 0.4462 / DE
F5 0.9077 0.9042 0.9279 0.9369 0.4292 EF
100 F1 0.5106 / / / / AB
F2 0.9754 0.5125 / / / BC
F3 0.9765 0.9134 0.5300 / / CD
F4 0.9460 0.9409 0.9075 0.4634 / DE
F5 0.9048 0.9487 0.9490 0.9447 0.5024 EF
500 F1 0.5188 / / / / AB
F2 0.9283 0.5202 / / / BC
F3 0.9657 0.9324 0.5297 / / CD
F4 0.9012 0.9170 0.9642 0.5188 / DE
F5 0.9034 0.9146 0.9496 0.9165 0.5084 EF