Table 17 Simulation results on the IEEE 30 bus system with overestimated Weibull probability distribution function of wind power on ORPD using different algorithms

From: Impact of the penetration of distributed generation on optimal reactive power dispatch

Control Variables (p.u.) PSO R-PSO L-PSO PSO-CFA IPSO-SR FOA MFOA JAYA
VG1 1.1 1.1 1.1 1.1 1.1 0.95 1.1 1.1
VG2 1.1 1.1 1.1 1.1 1.1 0.95 1.1 1.1
VG5 1.1 1.1 1.1 1.1 1.089 0.95 1.1 1.1
VG6 (DG) 1.1 1.1 1.1 1.1 1.1 0.95 1.1 1.1
VG8 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1
VG11 1.1 1.1 1.0998 1.1 1.1 0.95 1.1 1.1
VG13 1.1 1.0879 1.0692 1.0807 1.1 1.1 1.1 0.95
T6–9 1.1 1.1 1.1 1.1 1.1 0.9 0.9 1.1
T6–10 1.1 1.1 1.1 1.0852 1.1 0.9 0.9 0.9
T4–12 1.1 1.0965 1.1 1.1 1.1 1.1 0.9 0.9305
T28–27 1.0351 1.0243 1.0277 1.0427 1.0219 0.9 0.9 0.9532
Qsc3 0 0 0.0008 0.0008 0 0.003 0.0819 0.0897
Qsc10 0.3241 0.2143 0.1281 0.1945 0.2827 0.003 0.0818 0.3104
Qsc24 0.0753 0.1109 0.0983 0.1173 0.1038 0.003 0.0819 0.1244
Optimum DG value at bus no. 6 (MW) 2.3931 43.4629 48.4923 58.5706 6.5336 53.6444 58.7457 59.2683
Ploss (MW) 2.6374 2.6006 2.605 2.6157 2.5767 3.236 2.7915 2.4442