Skip to main content

Table 2 Parameters of DC filter

From: A fast boundary protection for an AC transmission line connected to an LCC-HVDC inverter station

Elements

HP12/24

HP3

C1/mF

0.35

0.8

L1/mH

89.35

11.99

C2/mF

0.81

1.825

L2/mH

48.86

964

R1

10,000

5700

Tuned frequency/Hz

600/1200

100/1950