Skip to main content

Table 1 Simulation results based on WTMM

From: Fault line selection in cooperation with multi-mode grounding control for the floating nuclear power plant grid

Fault forms

Fault 1

Fault 2

Fault 3

Results

Line 1

Optimal function

db3

db3

db10

Optimal scale

5

5

9

Square value

0.0758

0.0753

20.0580

Polarity

+

+

+

Line 2

Optimal function

db3

db3

db10

Optimal scale

5

5

9

Square value

0.3034

0.3014

74.8303

Polarity

+

+

+

Line 3

Optimal function

db3

db3

db10

Optimal scale

5

4

9

Square value

40.2709

35.5729

4407.7

Polarity

Line 4

Optimal function

db3

db3

db10

Optimal scale

5

5

9

Square value

0.3671

0.3647

93.2945

Polarity

+

+

+

Selection result

Line3

Line3

Line3

Whether correct

Correct

Correct

Correct