Skip to main content

Table 6 Protection characteristic parameters in other cases

From: Fault protection method of single-phase break for distribution network considering the influence of neutral grounding modes

Type

Ungrounded

Arc suppression coil grounded

Low resistance grounded

UO(V)

∆Iφ(A)

n1

UO(V)

∆Iφ(A)

n1

UO(V)

∆Iφ(A)

n1

Single phase grounding

5523.9

25.1

0.34

5482.7

5.2

0.86

5345.3

454.5

0.93

Two-phase short circuit

16.3

21,607

1.04

141.7

21,607

1.04

2.0

21,607

1.04

Load disappearance

23.8

− 804.1

5426.7

216.4

−804.1

5426.7

2.9

−804.1

5426.7