Skip to main content

Table 5 Fault locations and tie switching in IEEE 33 bus distribution network

From: Augmentation of situational awareness by fault passage indicators in distribution network incorporating network reconfiguration

Faulted line

FPI flag status

Fault impedance range (Ω)

Power loss after the fault (no tie switching) in kW

Tie closed

Power losses after the fault (with tie switching) in kW

Tie chosen on the basis of minimum power loss (kW)

% Loss reduction on comparing power loss after fault without tie switching & with tie switching

F4

F3

F2

F1

A23

0

1

0

1

1.2030–2.34720

910.03600

A37

172.1304

A37

(172.1304)

81.0353

A27

1

0

0

1

3.1236–4.53540

834.10000

A37

132.8096

A37

(132.8096)

84.0774

A36

141.0619

A14

0

0

0

1

9.8846–10.6757

384.50340

A36

114.0669

A34

(92.39790)

75.9695

A34

92.39790

A10

0

0

0

1

6.5203–6.72730

617.26090

A36

139.3396

A35

(73.88150)

88.0307

A34

76.35050

A35

73.88150

A7

0

0

0

1

3.2233–3.97250

933.05120

A36

166.6502

A35

(73.00310)

92.1796

A35

73.00310

A33

75.46760

A4

0

0

0

1

1.0673–1.49490

1243.9911

A37

143.5136

A37

(143.5136)

88.4634

A35

157.8183

A33

160.3537

A19

0

0

1

1

0.3300–2.35470

353.12300

A33

95.59170

A35

(91.92680)

73.9674

A35

91.92680