Table 5 Measured admittance results when the F1 fault occurs

From: New protection scheme for internal fault of multi-microgrid

Feeder Terminal Δφi(o) Δφ(o) |G1i| Feeder Terminal Δφi(o) Δφ(o) |G1i|
EG E − 41.50 −48.64 1.467 L5 X 158.67 −14.25 0.004
G −22.12 150.99 0.149 L6 Z −1.54 0.22 0.009
L1 C −1.12 0.01 0.015 L7 N 171.36 −3.74 0.008
L2 F 156.15 −17.67 0.015 TY T −15.32 −13.39 0.006
L3 H −1.54 −0.05 0.012 Y 172.58 −4.34 0.006
L4 R −1.58 0.18 0.012 L8 Q −1.76 −0.1 0.012
KP K 140.45 − 29.76 0.007 AD A −34.7 −34.3 0.729
P −20.16 −18.13 0.007 D 138.88 −35.8 1.479
JL J −19.35 − 17.54 0.025 MS M −10.58 −8.64 0.018
L 160.82 −15.28 0.024 S 169.23 −8.67 0.018