Table 6 Fault location results for single faults on transposed lines

From: Wide area measurements based fault detection and location method for transmission lines

Faulted lines Fault types Actual FL (p.u.) Fault Res. (Ω) FL Est. error (%) using data from selected buses
1 1 & 16
4–10 AG 0.8 1 0.01 0.01
4–10 AG 0.8 15 0.01 0.01
6–9 BC 0.3 1 0.43 0.05
4–10 BC 0.5 1 0.00 0.01
4–10 ABC 0.2 1 0.00 0.00
4–10 BCG 0.3 20 0.00 0.01
9–10 BG 0.9 15 0.01 0.36
9–10 BC 0.2 1 0.35 0.00
9–10 ABC 0.7 1 0.01 0.12