From: Wide area measurements based fault detection and location method for transmission lines
Faulted lines | Fault types | Actual FL (p.u.) | Fault Res. (Ω) | FL Est. error (%) using data from selected buses | |
---|---|---|---|---|---|
1 | 1 & 16 | ||||
4–10 | AG | 0.8 | 1 | 0.01 | 0.01 |
4–10 | AG | 0.8 | 15 | 0.01 | 0.01 |
6–9 | BC | 0.3 | 1 | 0.43 | 0.05 |
4–10 | BC | 0.5 | 1 | 0.00 | 0.01 |
4–10 | ABC | 0.2 | 1 | 0.00 | 0.00 |
4–10 | BCG | 0.3 | 20 | 0.00 | 0.01 |
9–10 | BG | 0.9 | 15 | 0.01 | 0.36 |
9–10 | BC | 0.2 | 1 | 0.35 | 0.00 |
9–10 | ABC | 0.7 | 1 | 0.01 | 0.12 |