Skip to main content

Table 3 DSE performance variation, fault time of variation in θse at Vse = 5% of UPFC

From: A critical fault detection analysis & fault time in a UPFC transmission line

Type Of Fault in phase

θse in deg.

Fault Condition-1: 100 km from bus B-S(before UPFC) Rf = 1 Ω, FIA = 00 NSI, Vse = 5%

Fault Condition-2: 300 km from Bus B-S (after UPFC) Rf = 1 Ω, FIA = 00,NSI, Vse = 5%

Fault time in cycle

A

B

C

A

B

C

 

A-G

0

116.2

9.11

3.80

−119.5

−35.21

−20.41

Ë‚1

AB-G

45

113.1

111.953

23.13

−46.2

−102.33

1.22

Ë‚1

ABC

60

63.25

115.33

111.38

−103.56

−105.09

−100.0

Ë‚1

BC G

90

30

111.30

115.04

−0.31

−102.41

−102.2

Ë‚1