Table 7 Time response specifications of two area system

From: Interconnected multi-machine power system stabilizer design using whale optimization algorithm

#Gen Specifications PSO DE WOA
G 1 %Peak overshoot 537.50 523.6 518.55
Settling time (sec) 2.9935 2.374 1.6879
G 2 %Peak overshoot 1211.3 712.5 680.21
Settling time (sec) 2.8499 2.748 1.5374
G 3 %Peak overshoot 1516.0 1491. 1379.5
Settling time (sec) 3.8991 3.397 3.9100
G 4 %Peak overshoot 2828.5 2366 2278.3
Settling time (sec) 3.0566 2.956 2.7717