Table 4 Series resistance, series reactance and shunt capacitance matrices of the 34.5 kV μGrid circuit

From: Protection and control of microgrids using dynamic state estimation

Parameter

Value

Series resistance matrix (per mile)

\( \left[\begin{array}{cccc}0.1818& 0.0924& 0.0924& 0.0922\\ {}0.0924& 0.1818& 0.0924& 0.0922\\ {}0.0924& 0.0924& 0.1818& 0.0922\\ {}0.0922& 0.0922& 0.0922& 0.1818\end{array}\right]\Omega / mi \)

Series reactance matrix (per mile)

\( \left[\begin{array}{cccc}3.5842& 2.1146& 2.1146& 1.9353\\ {}2.1146& 3.5842& 1.8918& 1.8802\\ {}2.1146& 1.8918& 3.5842& 1.8992\\ {}1.9353& 1.8802& 1.8992& 3.5842\end{array}\right] mH/ mi \)

Shunt capacitance matrix (per mile)

\( \left[\begin{array}{cccc}8.4066& -2.3555& -2.3417& -1.0823\\ {}-2.3555& 7.7689& -1.1427& -1.0362\\ {}-2.3417& -1.1427& 7.7943& -1.1056\\ {}-1.0823& -1.0362& -1.1056& 5.6988\end{array}\right] nF/ mi \)